Navvion Omega
Solar + storage + diesel hybrid with 20 ms grid switchover.
- 112–145 kWh
- Capacity Range
- 48–60 kW
- AC Power
- 20 ms
- Grid Switchover

Overview
Built for industrial reliability.
An integrated multi-functional C&I hybrid system with flexible single-unit capacity from 112 to 145 kWh. Supports PV and generator inputs plus grid-connected / off-grid switching — ideal for reliable backup in remote or unstable-grid sites.
20 ms grid switchover
When the grid fails, the system transfers to off-grid operation in 20 ms or less — fast enough that critical loads never see the outage.
Solar, storage, and diesel in one controller
Dual PV inputs (38.4 kW × 2) and generator support let one system orchestrate solar, batteries, and diesel across grid-connected and off-grid modes.
Parallel off-grid operation
Multiple subsystems run in parallel while off-grid, so capacity scales with the site and no single unit is a single point of failure.
Full unbalanced-load support
The output stage supports 100% unbalanced loads with THDv below 3% on linear loads — clean power for mixed single- and three-phase equipment.
Applications
Where this product works.
Every deployment links to Navvion APM.
Site onboarding, performance monitoring, alerts, warranty data, remote diagnostics, and service dispatch — from one console.
Trained installers. Local parts.
Deployment through certified partners, documented commissioning, APM onboarding, spare parts planning, and warranty/RMA workflows.
Specifications
Every parameter that matters.
| JG112A — Nominal Capacity | 112 kWh |
| JG112A — Rated Power (AC) | 48 kW |
| JG112A — AC Max Current | 76 A |
| JG112A — Weight | ~1.5 t |
| JG128A — Nominal Capacity | 128 kWh |
| JG128A — Rated Power (AC) | 55 kW |
| JG128A — AC Max Current | 87 A |
| JG128A — Weight | ~1.6 t |
| JG145A — Nominal Capacity | 145 kWh |
| JG145A — Rated Power (AC) | 60 kW |
| JG145A — AC Max Current | 96 A |
| JG145A — Weight | ~1.7 t |
| Max. Input Power | 38.4 kW × 2 |
| Max. Input Current | 64 A × 2 |
| Input Voltage | 200–800 V / 250 Vdc |
| Battery Type | LFP 3.2 V / 314 Ah |
| Max. Charge / Discharge | 150 A |
| PACK Configuration | 1P16S |
| AC Rated Voltage | 3P/N/PE; 230/400 V AC |
| Frequency | 50 / 60 Hz |
| Power Factor | 0.8 lead ~ 0.8 lag |
| THDi | < 5% (rated power) |
| THDv | < 3% (linear load) |
| Unbalanced Load | 100% |
| Switch Time | ≤ 20 ms |
| Dimensions (W×D×H) | 1088 × 1320 × 2300 mm |
| Cooling Method | Air Cooling |
| IP Rating | IP54 |
| Operating Temperature | -20 °C ~ +45 °C |
| Relative Humidity | 5 ~ 95% RH (non-cond.) |
| Altitude | ≤ 2000 m |
| Noise Emission | ≤ 75 dB |
| Fire Suppression | Aerosol |
| Standards | IEC/EN 62477-1 · IEC/EN 61000-6-2 · IEC/EN 61000-6-4 · IEC 62619 · G99 · G100 · AS4777.2 · EN 50549-1 · VDE-AR-N 4105 · UN38.3 |
Certifications
Aligned with international standards.
Navvion maintains a per-market certification roadmap covering documentation, testing, and local review.
Gallery
Around the system.

FAQ
Common questions.
Which models are available in the series?
Three single-unit capacities: JG112A (112 kWh / 48 kW), JG128A (128 kWh / 55 kW), and JG145A (145 kWh / 60 kW), all sharing the same hybrid architecture.
How fast is the transfer to backup power?
Switchover from grid-connected to off-grid operation completes in 20 ms or less, which most IT, control, and lighting loads ride through without interruption.
Can it work with an existing diesel generator?
Yes. The system supports generator input alongside PV and the grid, coordinating all three sources in a full solar-storage-diesel scenario.
How much solar can be connected?
Two PV inputs accept up to 38.4 kW each (64 A per input) across a 200–800 V input window, for up to 76.8 kW of connected PV per unit.
Does it scale for larger sites?
Multiple subsystems operate in parallel — including off-grid — so remote sites can grow capacity by adding units under the same monitoring platform.