Navvion
C&I Cabinet

Navvion Alpha

Air-cooling C&I cabinet, 257 kWh / 125 kW.

Model · ESS-C-JG257A-F2-2H0
257 kWh
Rated Capacity
125 kW
Rated Power
Air-Cooled
Thermal System
Navvion ESS-C-JG257A-F2-2H0 air-cooling C&I storage cabinet

Overview

Built for industrial reliability.

An air-cooled energy storage system for industrial parks and commercial sites. Large-capacity LFP cells with an advanced air-cooling solution and cabinet-level aerosol fire protection deliver safe, reliable operation.

01

Intelligent air cooling

The air-cooling system adjusts autonomously to load and ambient conditions, protecting the 314 Ah LFP cells without the maintenance profile of a liquid loop.

02

Plug-and-play commissioning

The cabinet arrives factory-configured with zero on-site debugging required — installers connect AC, communications, and ground, then energize.

03

Multi-layer protection

Cell, pack, and cabinet-level protections combine with aerosol fire suppression to keep faults isolated and the site safe.

04

257 kWh in one enclosure

High-capacity LFP cells deliver 257 kWh and 125 kW from a single IP54 outdoor cabinet — sized for commercial peak shaving and backup duty.

Applications

Where this product works.

Industrial parks
Commercial sites
Peak shaving
Backup power
Software Integration

Every deployment links to Navvion APM.

Site onboarding, performance monitoring, alerts, warranty data, remote diagnostics, and service dispatch — from one console.

Installation & Service

Trained installers. Local parts.

Deployment through certified partners, documented commissioning, APM onboarding, spare parts planning, and warranty/RMA workflows.

Specifications

Every parameter that matters.

AC Input / Output
Rated Power125 kW
Rated Voltage (AC)230 / 400 V, 3P+N+PE
Rated Frequency50 / 60 Hz
Power Factor0.8 lead ~ 0.8 lag
Battery Parameters
Rated Capacity257 kWh
Rated Voltage (DC)819.2 V
Voltage Range716.8 ~ 921.6 V
DC Max Current174 A
Battery TypeLFP 3.2 V / 314 Ah
Battery Module51.2 V / 16.07 kWh
System Configuration1P256S
General Data
Dimensions (W×D×H)2100 × 1500 × 2060 mm
Weight~2900 kg
Cooling MethodAir-Cooling
IP RatingIP54
Operating Temperature-20 °C ~ +45 °C
Relative Humidity5% ~ 95%
Altitude≤ 2000 m
Noise Emission≤ 75 dB
Fire SuppressionAerosol
Compliance
StandardsIEC/EN 62477-1 · IEC/EN 61000-6-2 · IEC/EN 61000-6-4 · IEC 62619 · G99 · G100 · AS4777.2 · EN 50549-1 · VDE-AR-N 4105 · UN38.3

Certifications

Aligned with international standards.

Navvion maintains a per-market certification roadmap covering documentation, testing, and local review.

IEC/EN 62477-1IEC/EN 61000-6-2IEC/EN 61000-6-4IEC 62619G99G100AS4777.2EN 50549-1VDE-AR-N 4105UN38.3
View certification matrix

FAQ

Common questions.

When should I choose air cooling over liquid cooling?

Air cooling suits sites that value simpler maintenance and lower auxiliary complexity; liquid cooling suits heavier daily cycling. Navvion engineers help match the thermal system to your load profile.

What does installation involve?

The cabinet is plug-and-play: it ships factory-configured, and certified installers complete placement, AC connection at 230/400 V, and commissioning without on-site debugging.

What operating environment does it support?

The cabinet operates from -20 °C to +45 °C, 5–95% relative humidity, and up to 2000 m altitude, with an IP54-rated enclosure for outdoor siting.

What safety systems are included?

Protection layers run from cell-level BMS supervision through pack and cabinet protections, with aerosol fire suppression built into the enclosure.

How is the cabinet monitored?

It connects to Navvion APM for performance monitoring, alarm management, and remote diagnostics — the same software stack used across the Navvion portfolio.