Navvion Alpha
Air-cooling C&I cabinet, 257 kWh / 125 kW.
- 257 kWh
- Rated Capacity
- 125 kW
- Rated Power
- Air-Cooled
- Thermal System

Overview
Built for industrial reliability.
An air-cooled energy storage system for industrial parks and commercial sites. Large-capacity LFP cells with an advanced air-cooling solution and cabinet-level aerosol fire protection deliver safe, reliable operation.
Intelligent air cooling
The air-cooling system adjusts autonomously to load and ambient conditions, protecting the 314 Ah LFP cells without the maintenance profile of a liquid loop.
Plug-and-play commissioning
The cabinet arrives factory-configured with zero on-site debugging required — installers connect AC, communications, and ground, then energize.
Multi-layer protection
Cell, pack, and cabinet-level protections combine with aerosol fire suppression to keep faults isolated and the site safe.
257 kWh in one enclosure
High-capacity LFP cells deliver 257 kWh and 125 kW from a single IP54 outdoor cabinet — sized for commercial peak shaving and backup duty.
Applications
Where this product works.
Every deployment links to Navvion APM.
Site onboarding, performance monitoring, alerts, warranty data, remote diagnostics, and service dispatch — from one console.
Trained installers. Local parts.
Deployment through certified partners, documented commissioning, APM onboarding, spare parts planning, and warranty/RMA workflows.
Specifications
Every parameter that matters.
| Rated Power | 125 kW |
| Rated Voltage (AC) | 230 / 400 V, 3P+N+PE |
| Rated Frequency | 50 / 60 Hz |
| Power Factor | 0.8 lead ~ 0.8 lag |
| Rated Capacity | 257 kWh |
| Rated Voltage (DC) | 819.2 V |
| Voltage Range | 716.8 ~ 921.6 V |
| DC Max Current | 174 A |
| Battery Type | LFP 3.2 V / 314 Ah |
| Battery Module | 51.2 V / 16.07 kWh |
| System Configuration | 1P256S |
| Dimensions (W×D×H) | 2100 × 1500 × 2060 mm |
| Weight | ~2900 kg |
| Cooling Method | Air-Cooling |
| IP Rating | IP54 |
| Operating Temperature | -20 °C ~ +45 °C |
| Relative Humidity | 5% ~ 95% |
| Altitude | ≤ 2000 m |
| Noise Emission | ≤ 75 dB |
| Fire Suppression | Aerosol |
| Standards | IEC/EN 62477-1 · IEC/EN 61000-6-2 · IEC/EN 61000-6-4 · IEC 62619 · G99 · G100 · AS4777.2 · EN 50549-1 · VDE-AR-N 4105 · UN38.3 |
Certifications
Aligned with international standards.
Navvion maintains a per-market certification roadmap covering documentation, testing, and local review.
Gallery
Around the system.

FAQ
Common questions.
When should I choose air cooling over liquid cooling?
Air cooling suits sites that value simpler maintenance and lower auxiliary complexity; liquid cooling suits heavier daily cycling. Navvion engineers help match the thermal system to your load profile.
What does installation involve?
The cabinet is plug-and-play: it ships factory-configured, and certified installers complete placement, AC connection at 230/400 V, and commissioning without on-site debugging.
What operating environment does it support?
The cabinet operates from -20 °C to +45 °C, 5–95% relative humidity, and up to 2000 m altitude, with an IP54-rated enclosure for outdoor siting.
What safety systems are included?
Protection layers run from cell-level BMS supervision through pack and cabinet protections, with aerosol fire suppression built into the enclosure.
How is the cabinet monitored?
It connects to Navvion APM for performance monitoring, alarm management, and remote diagnostics — the same software stack used across the Navvion portfolio.
Product Family